DESCRIPTION
Automatic A/C-heater system consists of a standard A/C-heater system and added electronically controlled components. The A/C-heater system is controlled by air mix door control, fan speed control, outlet door control, intake door control, A/C compressor clutch and memory function. Coolant temperature in heater core is monitored by heater core coolant temperature sensor.
OPERATION
Automatic A/C-heater system automatically selects optimum airflow, outlet air temperature and outlet vent to maintain vehicle interior temperature at desired setting.
Checks Operation Of Each Actuator
- With system in self-diagnosis step 3, set temperature switch to "D" position on auto amplifier to enter «SELF-DIAGNOSIS STEP»(ref-35301-S29510138372001010900000) 4. Fluorescent display will illuminate a "41". Each time defrost button is pressed, fluorescent display to right of "4" will advance one number, up to "46". After "46", the numbers begin again at "41".
- Ensure fresh air lever is off during tests. As numbers advance, the commands will change air intake and outlet routes. A visual and physical inspection must be made to ensure doors are switching properly. To determine proper door positions for each code, see «SELF-DIAGNOSIS STEP 4 CODE EXPLANATIONS»(ref-35301-S37754671562001010900000) table.
| Application | Door Position |
| Code 41 |
| Mode Door | Vent |
| Intake Door | Recirculate |
| Air Mix Door | Full Cold |
| Blower Motor | (1) Low (4-5 Volts) |
| Compressor | On |
| Max. Cold Door | Closed |
| Code 42 |
| Mode Door | Bi-Level |
| Intake Door | 20% Fresh Air |
| Air Mix Door | Full Cold |
| Blower Motor | (1) Middle High (9-11 Volts) |
| Compressor | On |
| Max. Cold Door | Open |
| Code 43 |
| Mode Door | Bi-Level |
| Intake Door | 20% Fresh Air |
| Air Mix Door | Full Hot |
| Blower Motor | (1) Middle Low (7-9 Volts) |
| Compressor | Off |
| Max. Cold Door | Open |
| Code 44 |
| Mode Door | (2) Foot/Defrost Mode 1 |
| Intake Door | 80% Fresh |
| Air Mix Door | Full Hot |
| Blower Motor | (1) Middle Low (7-9 Volts) |
| Compressor | Off |
| Max. Cold Door | Closed |
| Code 45 |
| Mode Door | (3) Foot/Defrost Mode 2 |
| Intake Door | Fresh |
| Air Mix Door | Full Hot |
| Blower Motor | (1) Middle Low (7-9 Volts) |
| Compressor | On |
| Max. Cold Door | Closed |
| Code 46 |
| Mode Door | Defrost |
| Intake Door | Fresh |
| Air Mix Door | Full Hot |
| Blower Motor | (1) High (10-12 Volts) |
| Compressor | On |
| Max. Cold Door | Closed |
| (1) Voltage applied to blower motor for desired speed. (2) Foot/Defrost Mode 1 is used when manual mode is selected on auto amplifier. More air (75 percent) is directed to feet. (3) Foot/Defrost Mode 2 is used when automatic mode is selected on auto amplifier. Less air (50 percent) is directed to feet. |
| (1) | Voltage applied to blower motor for desired speed. |
| (2) | Foot/Defrost Mode 1 is used when manual mode is selected on auto amplifier. More air (75 percent) is directed to feet. |
| (3) | Foot/Defrost Mode 2 is used when automatic mode is selected on auto amplifier. Less air (50 percent) is directed to feet. |
SELF-DIAGNOSIS STEP 4 CODE EXPLANATIONS