Scan Tool Output Controls
| Scan Tool Output Control | Additional Menu Selection(s) | Description |
|---|---|---|
| A/C Permission | Miscellaneous Tests | When you select ON, the HVAC control module changes the state of the A/C Permission parameter to Granted and transmits a clutch enable message to the PCM over the class 2 serial data circuit. The A/C compressor clutch engages and remains engaged until you select OFF. When you select OFF, the HVAC control module changes the state of the A/C Permission parameter to Withheld and transmits a clutch disable message to the PCM over the class 2 serial data circuit. |
| Air Inlet Door | Motor/Actuator Tests | When you select ON, the HVAC control module commands the recirculation actuator toward the maximum door position. The actuator moves the door to the recirculation position. When you select OFF, the HVAC control module commands the recirculation actuator toward the minimum door position. The actuator moves the door to the outside air position. |
| Blower Motor | Motor/Actuator Tests | When you select ON, the HVAC control module commands the blower motor to maximum speed. The blower motor operates at maximum speed until you select OFF. The HVAC control module must be in the ON state before selecting the output control. |
| HVAC Actuator Recalibration | When you select RESET, the HVAC control module recalibrates the maximum and minimum door positions of each HVAC door. The ambient air temperature display is set to the current value of the Outside Air Temp. Raw parameter. | |
| Inside Air Temperature Fan | Motor/Actuator Tests | When you select OFF, the HVAC control module commands the inside air temperature fan OFF. The fan remains OFF until you select ON. The normal state of the inside air temperature fan is ON. |
| Instant OAT Update | Miscellaneous Tests | The scan tool displays OFF or ON. This function updates the HVAC control module ambient air temperature input to the current raw value. |
| Left Mix Motor | Motor/Actuator Tests | When you select ON, the HVAC control module commands the left air temperature actuator toward the maximum door position. The actuator moves the door to the full hot position. When you select OFF, the HVAC control module commands the left air temperature actuator toward the minimum door position. The actuator moves the door to the full cold position. |
| Mode 1 Door Position | Motor/Actuator Tests | When you select ON, the HVAC control module commands the mode actuator toward the maximum door position. The actuator moves the door to the panel position. When you select OFF, the HVAC control module commands the mode actuator toward the minimum door position. The actuator moves the door to the floor position. |
| Right Mix Motor | Motor/Actuator Tests | When you select ON, the HVAC control module commands the right air temperature actuator toward the maximum door position. The actuator moves the door to the full cold position. When you select OFF, the HVAC control module commands the right air temperature actuator toward the minimum door position. The actuator moves the door to the full hot position. |
HVAC Control Module Scan Tool Output Controls
| Scan Tool Output Control | Additional Menu Selection(s) | Description |
|---|---|---|
| A/C Relay | Engine Output Controls | The engine must be running and the PCM must receive an A/C request from the HVAC control module in order to enable the output control. The PCM de-energizes the A/C compressor clutch relay when you select OFF. The relay remains de-energized until you select ON. |
PCM Scan Tool Output Controls
Scan Tool Data List
| Scan Tool Parameter | Data List | Units Displayed | Typical Data Value |
|---|---|---|---|
| Operating Conditions: Engine idling, A/C ON, ambient air temperature between 22-27° C (70-80° F) | |||
| Left Solar Sensor | Data | Counts/Volts | Varies |
| Right Solar Sensor | Data | Counts/Volts | Varies |
BCM Scan Tool Data List
| Scan Tool Parameter | Data List | Units Displayed | Typical Data Value |
|---|---|---|---|
| Operating Conditions: Engine idling, A/C ON, ambient air temperature between 22-27° C (70-80° F) | |||
| A/C Switch | Input/Output | On/Off | Off |
| AC Permission | Input/Output | Withheld/Granted | Varies |
| Air Inlet Door Actual | Door Positions | Counts | Varies |
| Air Inlet Commanded | Door Positions | Counts | Varies |
| Air Inlet Motor Drive | Door Positions | Stop, Increase, Decrease | Stop |
| Air Mix Door Left Commanded | Door Positions | Counts | Varies |
| Air Mix Door Right Commanded | Door Positions | Counts | Varies |
| Auto Switch | Input/Output | On/Off | Off |
| Battery Voltage | Input/Output | Volts | 13.5-14.5 V |
| Blower Motor PWM Speed | Door Positions | Percent | 12-114% |
| Dim Level Requested | Sensor Data | Percent | Varies |
| Engine Coolant Temp | Sensor Data | ° C/° F | Varies |
| Fan Down Button | Input/Output | On/Off | Off |
| Fan Up Button | Input/Output | On/Off | Off |
| Front Defrost Switch | Input/Output | On/Off | Off |
| Ign. Since Current DTC | Input/Output | Cycles | 0 |
| Inside Air Temp. Sensor | Sensor Data | ° C/° F | Varies |
| Inside Air Temp. Fan | Sensor Data | On/Off | On |
| Left Mix Door Actual | Door Positions | Counts | Varies |
| Left Mix Motor Drive | Door Positions | Stop, Increase, Decrease | Stop |
| Left Temp. Setting | Input/Output | ° C/° F | Varies |
| LH AC Duct Actual | Sensor Data | Counts | Varies |
| LH AC Duct Desired | Sensor Data | Counts | Varies |
| LH Heater Duct Actual | Sensor Data | Counts | Varies |
| LH Heater Duct Desired | Sensor Data | Counts | Varies |
| Mode Door Actual | Door Positions | Counts | Varies |
| Mode Dr. Motor Command | Door Positions | Counts | Varies |
| Mode Motor Drive | Door Positions | Stop, Increase, Decrease | Stop |
| Mode Select Position | Door Positions | Off, Auto, Defrost, Heater, Htr/Def, Bi-Level, Panel | Varies |
| Mode Switch | Input/Output | On/Off | Off |
| Off Switch | Input/Output | On/Off | Off |
| Outside Air Temp. Filtered | Input/Output | ° C/° F | 22-27° C (70-80° F) |
| Outside Air Temp. Raw | Input/Output | ° C/° F | Varies |
| Pressure Cycle Switch | Input/Output | Low Pressure, Normal | Varies |
| Rear Defrost Switch | Input/Output | On/Off | Off |
| Recirculate Switch | Input/Output | On/Off | Off |
| RH AC Duct Actual | Sensor Data | Counts | Varies |
| RH AC Duct Desired | Sensor Data | Counts | Varies |
| RH Heater Duct Actual | Sensor Data | Counts | Varies |
| RH Heater Duct Desired | Sensor Data | Counts | Varies |
| Right Mix Door Actual | Door Positions | Counts | Varies |
| Right Mix Motor Drive | Door Positions | Stop, Increase, Decrease | Stop |
| Right Temp. Setting | Input/Output | ° C/° F | Varies |
HVAC Control Module Scan Tool Data List
| Scan Tool Parameter | Data List | Units Displayed | Typical Data Value |
|---|---|---|---|
| Operating Conditions: Engine idling, A/C ON, ambient air temperature between 22-27° C (70-80° F) | |||
| A/C Pressure Sensor | Engine Data 2 | KPa/Psi | 629-845 kPa (85-120 psi) |
| A/C Pressure Sensor | Engine Data 2 | Volts | Varies |
| A/C Relay Command | Engine Data 2 | On/Off | Varies |
| A/C Request Signal | Engine Data 2 | Yes/No | Varies |
| ECT Sensor | Engine Data 2 | ° C/° F | 92° C (197° F) |
PCM Scan Tool Data List
Diagnostic Trouble Code (DTC) List
| DTC | Diagnostic Procedure | Module |
|---|---|---|
| B0159 | DTC B0159 | HVAC Control Module |
| B0164 | DTC B0164 | HVAC Control Module |
| B0174 | DTC B0174, B0179, B0510, or B0515 | HVAC Control Module |
| B0179 | DTC B0174, B0179, B0510, or B0515 | HVAC Control Module |
| B0183 | DTC B0183 or B0188 | BCM |
| B0188 | DTC B0183 or B0188 | BCM |
| B0229 | DTC B0229, B0414, B0424, or B3770 | HVAC Control Module |
| B0263 | DTC B0263, B0268, B0408, or B0418 | HVAC Control Module |
| B0268 | DTC B0263, B0268, B0408, or B0418 | HVAC Control Module |
| B0408 | DTC B0263, B0268, B0408, or B0418 | HVAC Control Module |
| B0414 | DTC B0229, B0414, B0424, or B3770 | HVAC Control Module |
| B0418 | DTC B0263, B0268, B0408, or B0418 | HVAC Control Module |
| B0424 | DTC B0229, B0414, B0424, or B3770 | HVAC Control Module |
| B0510 | DTC B0174, B0179, B0510, or B0515 | HVAC Control Module |
| B0515 | DTC B0174, B0179, B0510, or B0515 | HVAC Control Module |
| B1375 | DTC B1375 | HVAC Control Module |
| B3770 | DTC B0229, B0414, B0424, or B3770 | HVAC Control Module |
| P0530 | DTC P0530 | Powertrain Control Module |
Diagnostic Trouble Code (DTC) List
Circuit Description
The ambient air temperature sensor allows the HVAC control module to monitor the temperature of the air surrounding the front of the vehicle. The module applies 5 volts to internal input resistors that are connected to the signal circuit of the ambient air temperature sensor. The module provides ground to the ambient air temperature sensor through the low reference circuit. The HVAC control module monitors the voltage drop across the ambient air temperature sensor and uses the input for automatic control calculations. When the air temperature is cold, the resistance of the sensor is high and the voltage signal is high. When the air temperature is hot, the resistance of the sensor is low and the voltage signal is low.
Conditions for Running the DTC
- Battery voltage to the HVAC control module is greater than 8.7 V and less than 16.5 V.
- The ignition is turned ON.
Conditions for Setting the DTC
The HVAC control module determines that the voltage applied to the input for the ambient air temperature sensor is less than 0.09 V or greater than 4.9 V.
Action Taken When the DTC Sets
The scan tool displays 10° C (50° F) as the value for the Outside Air Temp. Raw parameter.
Conditions for Clearing the DTC
- The DTC will become history if the HVAC control module no longer detects the condition that set the DTC.
- The history DTC will clear after 100 fault free ignition cycles.
- The DTC can be cleared with a scan tool.
Diagnostic Aids
If the condition is not present, refer to Testing for Intermittent Conditions and Poor Connections in Wiring Systems.
The inside air temperature sensor assembly allows the HVAC control module to monitor the temperature of the air inside the passenger compartment. The module applies 5 volts to internal input resistors that are connected to the signal circuit of the inside air temperature sensor assembly. The module provides ground to the inside air temperature sensor assembly through the low reference circuit. The HVAC control module monitors the voltage drop across the inside air temperature sensor assembly and uses the input for automatic control calculations. When the air temperature is cold, the resistance of the sensor is high and the voltage signal is high. When the air temperature is hot, the resistance of the sensor is low and the voltage signal is low.
- Battery voltage to the HVAC control module is greater than 8.7 V and less than 16.5 V.
- The ignition is turned ON.
The HVAC control module determines that the voltage applied to the input for the inside air temperature sensor assembly is less than 0.09 V or greater than 4.9 V.
The HVAC control module uses a default value of 55° C (131° F) for the Inside Air Temp. parameter. This value will be displayed on the scan tool.
- The DTC will become history if the HVAC control module no longer detects the condition that set the DTC.
- The history DTC will clear after 100 fault free ignition cycles.
- The DTC can be cleared with a scan tool.
If the condition is not present, refer to Testing for Intermittent Conditions and Poor Connections in Wiring Systems.
The following DTC's are for the air temperature sensors located in the discharge air ducts
- B0174 is for the upper left air temperature sensor.
- B0179 is for the lower left air temperature sensor.
- B0510 is for the upper right air temperature sensor.
- B0515 is for the lower right air temperature sensor.
Air temperature sensors allow the HVAC control module to monitor the temperature of the discharge air in the HVAC ducts. The module applies 5 volts to internal input resistors that are connected to the signal circuits of the air temperature sensors. The module provides ground to the air temperature sensors through the low reference circuit. The HVAC control module monitors the voltage drop across the air temperature sensors and uses the inputs for automatic control calculations. When the duct air temperatures are cold, the resistances of the sensors are high and the voltage signals are high. When the duct air temperatures are hot, the resistances of the sensors are low and the voltage signals are low. The HVAC control module converts the voltage values to count values where 1 V is approximately equal to 51 counts.
- Battery voltage is within 8.7-16.5 V.
- The ignition is ON.
The HVAC control module determines that the value of the air temperature parameter is less than 5 counts or greater than 250 counts.
The HVAC control module uses a default air temperature value for further automatic control calculations. The default values are not displayed on the scan tool.
- The DTC will become history if the HVAC control module no longer detects a fault.
- The history DTC will clear after 100 fault free ignition cycles.
- The DTC can be cleared with a scan tool.
If the condition is not present, refer to Testing for Intermittent Conditions and Poor Connections in Wiring Systems.
The following DTC's are for the left and right sunload sensors.
- B0183 is for the left sunload sensor.
- B0188 is for the right sunload sensor.
The left and right sunload sensors provide the HVAC control module with inputs as to the amount heat load the sun is placing on the interior of the vehicle. The sunload sensors are photodiodes that are sensitive to light intensity. The body control module (BCM) applies 5 volts to internal input resistors that are connected to the left and right signal circuits of the sunload sensor assembly. The BCM provides ground to the sensors through the low reference circuit. The BCM monitors the voltage drops across the sunload sensors and converts the voltage values to count values where 1 V is approximately equal to 51 counts. As the light intensity increases, the sunload sensors allow more current to travel through the circuits and the signal voltages decrease. As the light intensity decreases, the sunload sensors allow less current to travel through the circuits and the signal voltages increase. The BCM transmits the data to the HVAC control module over the class 2 serial data circuit.
The ignition is ON.
The BCM determines that the value of the sunload sensor signal is less than 5 counts or greater than 250 counts.
The action taken will be for the BCM to revert to a calibrated default value.
- The DTC will become history if the BCM no longer detects a failure.
- The history DTC will clear after 100 fault free ignition cycles.
- The DTC can be cleared with a scan tool.
If condition not present, refer to Testing for Intermittent Conditions and Poor Connections in Wiring Systems.
The following DTC's are for the HVAC door actuators
- B0229 is for the recirculation actuator.
- B0414 is for the left air temperature actuator.
- B0424 is for the right air temperature actuator.
- B3770 is for the mode actuator.
The HVAC control module controls the HVAC door actuators to regulate the airflow through the HVAC system. Each actuator consists of a stepper motor, a logic circuit, and a potentiometer. The potentiometer inside the door actuator allows the module to monitor the current position of the actuator drive shaft. The module supplies a 5 volt source voltage to the potentiometer on the 5 volt reference circuit. The module supplies ground to the potentiometer through the low reference circuit. The HVAC control module monitors the voltage drop across the potentiometer on the door position signal circuit. When the actuator shaft rotates, the voltage on the door position signal circuit changes. The module converts the voltage value to a count value where 1 volt is approximately equal to 51 counts.
The HVAC control module calibrates the travel range of the HVAC door actuators when it is initially powered by the battery positive voltage circuit. During calibration, the module commands the actuators in each direction until door travel is stopped. The module stores the minimum door positions and the maximum door positions of each actuator into memory. The total travel range is calculated by subtracting the minimum door position from the maximum door position. The door actuators can be calibrated again with a scan tool.
- Battery voltage is 8.7-16.5 volts.
- The ignition is ON.
The DTC sets when one of the following conditions are present
- The actual door position value for the actuator is less than 5 counts.
- The actual door position value for the actuator is greater than 250 counts.
- The actuator fails calibration because the calculated travel range value is too great or too small.
- If the DTC sets because the actual door position value is out of range, the HVAC control module will command the actuator to a default position.
- If the DTC sets because the actuator failed a calibration, the HVAC control module will attempt to calibrate the motor in the next transition from OFF to RUN mode.
- The DTC will become history if the HVAC control module no longer detects the condition that set the DTC.
- The history DTC will clear after 100 fault free ignition cycles.
- The DTC can be cleared with a scan tool.
- If the condition is not present refer to «Testing for Intermittent Conditions and Poor Connections»(ref-187209-S18750056402005083100000) in Wiring Systems.
- If the DTC sets following a calibration of the door actuator, inspect the door and the actuator for the following conditions: A misaligned actuator Broken linkages or binding linkages A broken door or a binding door An obstruction that prevents the door from operating within the full range of motion Missing seals to the door Poor connections at the harness connector of the door actuator
The following DTC's are for the HVAC door actuators
- B0263 is for the mode actuator.
- B0268 is for the recirculation actuator.
- B0408 is for the left air temperature actuator.
- B0418 is for the right air temperature actuator.
The HVAC control module controls the HVAC door actuators to regulate the airflow through the HVAC system. Each actuator consists of a stepper motor, a logic circuit, and a potentiometer. The potentiometer inside the door actuator allows the module to monitor the current position of the actuator drive shaft. The logic circuit inside the actuators receives control signals from the HVAC control module and controls the internal stepper motor. When a door positional change is required, the HVAC control module calculates a commanded door position. The module compares the commanded door position to the actual door position and determines the needed direction of motor rotation. The module applies a signal voltage to the door control circuit that is an input to the internal logic circuit of the door actuator. A 5 volt signal increases the door position. A 0 volt signal decreases the door position. When the commanded door position is equal to the actual door position, the HVAC control module sends a 2.5 volt signal to the door actuator and motor rotation stops. The ignition 3 voltage circuit provides source voltage to the logic circuit. The module provides ground to the actuator logic circuit through the low reference circuit.
- Source voltage is 8.7-16.5 volts.
- The ignition is ON.
- The HVAC control module commands the actuator to move.
The actual door position is not near the commanded door position.
The HVAC control module does not command the actuator to move for the remainder of the ignition cycle.
- The DTC becomes history during the next ignition cycle in which the HVAC control module no longer detects a stall condition.
- The history DTC will clear after 100 fault free ignition cycles.
- The DTC can be cleared with a scan tool.
- If the condition is not present refer to «Testing for Intermittent Conditions and Poor Connections»(ref-187209-S18750056402005083100000) in Wiring Systems.
- Inspect the appropriate door and door actuator for the following conditions: A misaligned door actuator Binding linkages A binding door An obstruction that prevents the door actuator from operating within the full range of motion
The ignition 3 voltage circuit is a discrete input to the HVAC control module. The HVAC control modules uses the input to determine that the ignition switch is in the RUN position. When the ignition switch is in the RUN position, ignition voltage is applied to the input.
- Source voltage is 8.7-16.5 volts.
- The HVAC control module receives a RUN power mode message from the BCM over the class 2 serial data circuit.
The HVAC control module does not detect ignition voltage on the ignition 3 voltage input.
The HVAC control module will continue to operate using the class 2 power mode messaging.
- The DTC will become history if the HVAC control module no longer detects the condition that set the DTC.
- The history DTC will clear after 100 fault free ignition cycles.
- The DTC can be cleared with a scan tool.
| Step | Action | Yes | No |
|---|---|---|---|
| Schematic Reference: HVAC Schematics Connector End View Reference: HVAC Connector End Views | |||
| 1 | Did you perform the HVAC Diagnostic System Check? | Go to Step 2 | Go to Diagnostic System Check - HVAC Systems - Automatic |
| 2 | Install a scan tool. Turn ON the ignition, with the engine OFF. Select the HVAC control module display DTC function on the scan tool. Does the scan tool indicate that B1375 is a current DTC? | Go to Step 3 | Go to Testing for Intermittent Conditions and Poor Connections in Wiring Systems |
| 3 | Turn OFF the ignition. Disconnect the HVAC control module. Turn ON the ignition, with the engine OFF. Probe the ignition 3 voltage circuit with a test lamp that is connected to a good ground. Does the test lamp illuminate? | Go to Step 4 | Go to Step 5 |
| 4 | Inspect for poor connections at the harness connector of the HVAC control module. Refer to Testing for Intermittent Conditions and Poor Connections and Connector Repairs in Wiring Systems. Did you find and correct the condition? | Go to Step 7 | Go to Step 6 |
| 5 | Repair the ignition 3 voltage circuit. Refer to Wiring Repairs in Wiring Systems. Did you complete the repair? | Go to Step 7 | |
| 6 | Replace the HVAC control module. Refer to HVAC Control Module Replacement . Did you complete the replacement? | Go to Step 7 | |
| 7 | Use the scan tool in order to clear the DTCs. Operate the vehicle within the Conditions for Running the DTC as specified in the supporting text. Does the DTC reset? | Go to Step 3 | System OK |
DTC B1375
The powertrain control module (PCM) monitors the high side refrigerant pressure via a A/C refrigerant pressure sensor. When the pressure is high the signal voltage is high. When the pressure is low the signal voltage is low. When pressure is too high the PCM will not allow the A/C compressor clutch to engage.
The PCM detects an A/C request.
- The A/C refrigerant pressure sensor signal is less than 0.1 volts for 5 seconds.
- The A/C refrigerant pressure sensor signal is greater than 4.9 volts for 5 seconds.
The malfunction indicator lamp (MIL) will not illuminate.
- The DTC will become history if the PCM no longer detects a failure.
- The history DTC will clear after 40 fault-free ignition cycles.
- The DTC can be cleared with a scan tool.
For an intermittent, refer to Testing for Intermittent Conditions and Poor Connections in Wiring Systems.
Visual/Physical Inspection
- Inspect for aftermarket devices which could affect the operation of the HVAC System. Refer to «Checking Aftermarket Accessories»(ref-187209-S27288891182005083100000) in Wiring Systems.
- Inspect the easily accessible or visible system components for obvious damage or conditions which could cause the symptom.
- Verify the A/C compressor clutch turns freely and is not seized.
- Verify that the customer is using the correct key to enable personalization.
- The A/C compressor will not operate in cold outside air temperatures. Refer to «Air Temperature Description and Operation»(ref-187235-S20090950652005083100000) .
- The following conditions may cause window fogging: Wet carpet or mats High humidity Interior water leak Blocked A/C evaporator drain tube Maximum passenger capacity Blocked body pressure relief valves
- Inspect the air distribution system for causes of reduced air flow: Obstructed or dirty passenger compartment air filter, if equipped Blocked or damaged air inlet or outlet vents
Symptom List
Refer to a symptom diagnostic procedure from the following list in order to diagnose the symptom
- «HVAC Compressor Clutch Does Not Engage»(ref-187235-S20450202632005083100000)
- «HVAC Compressor Clutch Does Not Disengage»(ref-187235-S09754149882005083100000)
- «Blower Motor Always On»(ref-187235-S13523725712005083100000)
- «Blower Motor Inoperative»(ref-187235-S40875835372005083100000)
- «Blower Motor Malfunction»(ref-187235-S41448839612005083100000)
- «Too Hot in Vehicle»(ref-187235-S36376344822005083100000)
- «Too Cold in Vehicle»(ref-187235-S35997412222005083100000)
- «Air Delivery Improper»(ref-187235-S08291359432005083100000)
- «Air Recirculation Malfunction»(ref-187235-S14202194732005083100000)
- «Leak Testing»(ref-187267-S13262864282005083100000) in Heating, Ventilation and Air Conditioning
- «Noise Diagnosis - Blower Motor»(ref-187267-S15172595182005083100000) in Heating, Ventilation and Air Conditioning
- «Noise Diagnosis - Air Conditioning (A/C) System»(ref-187267-S35538374732005083100000) in Heating, Ventilation and Air Conditioning
- «Noise Diagnosis - HVAC Module»(ref-187267-S33188364762005083100000) in Heating, Ventilation and Air Conditioning
- «Odor Diagnosis»(ref-187267-S32158253452005083100000) in Heating, Ventilation and Air Conditioning
A/C compressor clutch will not engage under the following conditions
- The A/C high side line pressure is over 2957 kPa (429 psi).
- The A/C low side line pressure is under 138-172 kPa (20-25 psi).
To accurately determine what pressure the A/C low pressure switch opens and closes at, use Kent Moore GE-47742 which will allow the technician to measure the switch point pressure at the switch.
Using a scan tool, monitor the "low pressure switch" status while monitoring the "low side" pressure at the switch to determine the switch points of the low pressure switch.
The low pressure switch "connector seal" must be removed before plugging it into the switch for testing. The "plunger effect" of plugging the connector with seal into the switch induces a pressure on the back side of the switch, this pressure will skew the opening/closing characteristics of the switch 5-10 psi until the pressure bleeds off. The time required for the connection induced pressure to bleed off can take 20 minutes or longer.
- The condition may be intermittent. Refer to «Testing for Intermittent Conditions and Poor Connections»(ref-187209-S18750056402005083100000) in Wiring Systems.
- The air temperature actuators can be calibrated. Refer to «Re-Calibrating Actuators»(ref-187235-S04344226052005083100000) .
- If the door actuators are out of the calibrated range the auto recirculation function will not work. The vehicle operator must place the HVAC controls to the recirculation position manually. Ensure to perform an actuator recalibration to correct this condition.
- The condition may be intermittent. Refer to «Testing for Intermittent Conditions and Poor Connections»(ref-187209-S18750056402005083100000) in Wiring Systems.
- The air temperature actuators can be calibrated. Refer to «Re-Calibrating Actuators»(ref-187235-S04344226052005083100000) .
- The condition may be intermittent. Refer to «Testing for Intermittent Conditions and Poor Connections»(ref-187209-S18750056402005083100000) in Wiring Systems.
- Inspect the air delivery system for the following conditions: An obstruction to the airflow Air leaks Misaligned air ducts Broken or binding linkages or doors
| Step | Action | Yes | No |
|---|---|---|---|
| Schematic Reference: HVAC Schematics Connector End View Reference: HVAC Connector End Views | |||
| 1 | Did you perform the HVAC Diagnostic System Check? | Go to Step 2 | Go to Diagnostic System Check - HVAC Systems - Automatic |
| 2 | Turn ON the ignition, with the engine OFF. Place the blower motor switch in the OFF position. Is the blower motor OFF? | Go to Step 3 | Go to Blower Motor Always On |
| 3 | Place the blower motor switch in each speed position. Does the blower motor operate in any of the speed positions? | Go to Step 4 | Go to Blower Motor Inoperative |
| 4 | Does the blower motor operate in each speed position? | Go to Step 5 | Go to Blower Motor Malfunction |
| 5 | With a scan tool, observe the Mode Switch parameter in the Heating and Air Conditioning data list. Activate the mode switch. Does the scan tool indicate that the Mode Switch parameter changes state? | Go to Step 6 | Go to Step 7 |
| 6 | Place the blower motor switch in the maximum speed position. Place the mode switch in the bi-level position. Place the recirculation switch in the ON position. Observe the drive shaft of the recirculation actuator. Place the recirculation switch in the OFF position. Does the recirculation door move from the recirculation position to the outside air position? | Go to Diagnostic Aids | Go to Air Recirculation Malfunction |
| 7 | Inspect for poor connections at the harness connector of the HVAC control module. Refer to Testing for Intermittent Conditions and Poor Connections and Connector Repairs in Wiring Systems. Did you find and correct the condition? | Go to Step 9 | Go to Step 8 |
| 8 | Replace the HVAC control module. Refer to HVAC Control Module Replacement . Did you complete the replacement? | Go to Step 9 | |
| 9 | Operate the system in order to verify the repair. Did you correct the condition? | System OK | Go to Step 2 |
Air Delivery Improper